ZLJ-200G and ZLJ-400G bi-stable (latching) normally open DC contactors; 48–72 V DC.
ZLJ-200G and ZLJ-400G are bi-stable contactors that are closed and opened by a pulse; they need no continuous coil current to hold their position, which removes standby consumption in battery systems.
For the electrical control systems of telecom power supplies, construction machinery, electric forklifts, motor vehicles, rail, marine and UPS systems.

ZLJ-200G
Technical data, curves and dimension drawings are taken from the manufacturer's data sheet.
Technical Specifications
| Contact arrangement | 1H (SPST-NO) |
|---|---|
| Contact material | Ag alloy |
| Contact voltage drop | ≤ 80 mV at 200 A |
| Insulation resistance | Min. 100 MΩ at 500 V DC |
| Dielectric strength (between insulated parts) | 1000 V AC 50/60 Hz (1 min), leakage < 1 mA |
| Operate time | Max. 30 ms |
| Release time | Max. 30 ms |
| Mechanical life | 100,000 operations (no load) |
| Electrical life | 6,000 operations (at rated load) |
| Working duty | Continuous |
| Model No. | ZLJ-200 g/□ , ZLJ-200 g/B□ |
| Contact rating (resistive load) | 200 A × 48 V DC (DC-1) , 200 A × 72 V DC (DC-1) |



ZLJ-400G
Technical data, curves and dimension drawings are taken from the manufacturer's data sheet.
Technical Specifications
| Contact arrangement | 1H (SPST-NO) |
|---|---|
| Contact material | Ag alloy |
| Contact voltage drop | ≤ 80 mV at 400 A |
| Insulation resistance | Min. 100 MΩ at 500 V DC |
| Dielectric strength (between insulated parts) | 1000 V AC 50/60 Hz (1 min), leakage < 1 mA |
| Operate time | Max. 40 ms |
| Release time | Max. 40 ms |
| Mechanical life | 100,000 operations (no load) |
| Electrical life | 6,000 operations (at rated load) |
| Working duty | Continuous |
| Model No. | ZLJ-400 g/□ , ZLJ-400 g/B□ |
| Contact rating (resistive load) | 400 A × 48 V DC (DC-1) , 400 A × 72 V DC (DC-1) |