Changeover ZLJM-D 1Z (SPDT) and 2Z (DPDT) DC contactors; 125, 200 and 400 A.
The ZLJM-D 1Z (single-pole) and 2Z (double-pole) models are changeover contactors that transfer a load between two sources or two circuits. They are used for battery / mains transfer, motor reversing and redundant supply circuits.
For the electrical control systems of telecom power supplies, construction machinery, electric forklifts, motor vehicles, rail, marine and UPS systems.
ZLJM-125D 1Z Switching capacity — 125 ACoil power — max. 12 WTechnical Specifications Model No. ZLJM-125D 1Z Contact arrangement 2H (DPST-NO) Contact material AgCdO(12) Contact rating (resistive load) 125 A 80 V DC / 125 A 250 V AC Max. switching voltage 80 V DC, 250 V AC Max. switching power 25,000 VA (AC); 10,000 VA (DC) Overload endurance (7 Ie / 10 s) 875 A / 10 s Coil rated voltage 12, 24, 48, 60, 72, 120 V DC, etc. Pick-up voltage 40–70 % of rated coil voltage Drop-out voltage 5–30 % of rated coil voltage Contact voltage drop ≤ 80 mV at 100 A Insulation resistance Min. 100 MΩ at 500 V DC Dielectric strength (between insulated parts) 1000 V AC 50/60 Hz (1 min) Operate time Max. 50 ms Release time Max. 50 ms Ambient temperature -25 … +60 °C Vibration resistance 10–200 Hz, acceleration ≤ 3.5 g Shock resistance 60–100 shocks/min, acceleration ≤ 4 g Mechanical life 100,000 operations (no load) Electrical life 10,000 operations (at rated load)
Manufacturer Product Page
ZLJM-125D 2Z Switching capacity — 125 ACoil power — max. 16 WTechnical Specifications Model No. ZLJM-125D/2Z Contact arrangement DPDT Contact material AgCdO Contact rating (resistive load) 125 A 48 V DC / 125 A 250 V AC Max. switching voltage 60 V DC, 250 V AC Overload endurance (7 Ie / 10 s) 875 A / 10 s Coil rated voltage 12, 24, 36, 48, 60, 120 V DC, etc. Drop-out voltage 5–30 % of rated coil voltage Contact resistance Max. 50 mΩ (initial) Insulation resistance Min. 100 MΩ at 500 V DC Dielectric strength (between insulated parts) 1000 V AC 50/60 Hz (1 min) Operate time Max. 50 ms Release time Max. 50 ms Ambient temperature -25 … +40 °C Relative humidity up to 98 % at +20 °C Electrical life 6,000 operations Mechanical life 100,000 operations Mounting direction Vertical or horizontal; coil at the bottom when mounted vertically
Manufacturer Product Page
ZLJM-200D 1Z Switching capacity — 200 ACoil power — max. 15 WApprovals — UL (E145623)Technical Specifications Model No. ZLJM-200D/1Z Contact arrangement SPDT Contact material AgCdO Contact rating (resistive load) 200 A 80 V DC / 200 A 250 V AC Max. switching voltage 80 V DC, 250 V AC Max. switching power 50,000 VA Overload endurance (7 Ie / 10 s) 1400 A / 10 s Coil rated voltage 12, 24, 48, 60, 120 V DC, etc. Pick-up voltage 40–70 % of rated coil voltage Drop-out voltage 5–30 % of rated coil voltage Contact voltage drop ≤ 30 mV at 100 A Insulation resistance Min. 100 MΩ at 500 V DC Dielectric strength (between insulated parts) 1000 V AC 50/60 Hz (1 min) Operate time Max. 50 ms Release time Max. 50 ms Ambient temperature -25 … +60 °C Vibration resistance 10–200 Hz, acceleration ≤ 3.5 g Shock resistance 60–100 shocks/min, acceleration ≤ 4 g Mechanical life 100,000 operations (no load) Electrical life 50,000 operations (at rated load)
Manufacturer Product Page
ZLJM-200D 2Z Switching capacity — 200 ACoil power — max. 16 WTechnical Specifications Model No. ZLJM-200D/2Z Contact arrangement DPDT Contact material AgCdO Contact rating (resistive load) 200 A 60 V DC / 200 A 250 V AC Max. switching voltage 60 V DC, 250 V AC Overload endurance (7 Ie / 10 s) 1400 A / 10 s Coil rated voltage 12, 24, 36, 48, 60, 120 V DC, etc. Drop-out voltage 5–30 % of rated coil voltage Contact resistance Max. 50 mΩ (initial) Insulation resistance Min. 100 MΩ at 500 V DC Dielectric strength (between insulated parts) 1000 V AC 50/60 Hz (1 min) Operate time Max. 50 ms Release time Max. 50 ms Ambient temperature -25 … +40 °C Relative humidity up to 98 % at +20 °C Electrical life 6,000 operations Mechanical life 100,000 operations Mounting direction Vertical or horizontal; coil at the bottom when mounted vertically
Manufacturer Product Page
ZLJM-400D 1Z Switching capacity — 400 ACoil power — max. 15 WApprovals — UL (E145623)Technical Specifications Model No. ZLJM-400D/1Z Contact arrangement SPDT Contact material AgCdO(12) Contact rating (resistive load) 400 A 60 V DC / 400 A 250 V AC Max. switching voltage 80 V DC, 250 V AC Max. switching power 10,000 VA Overload endurance (7 Ie / 10 s) 2800 A / 10 s Coil rated voltage 12, 24, 48, 60, 120 V DC, etc. Pick-up voltage 40–70 % of rated coil voltage Drop-out voltage 5–30 % of rated coil voltage Contact voltage drop ≤ 30 mV at 100 A Insulation resistance Min. 100 MΩ at 500 V DC Dielectric strength (between insulated parts) 1500 V AC 50/60 Hz (1 min) Operate time Max. 50 ms Release time Max. 50 ms Ambient temperature -25 … +60 °C Vibration resistance 10–200 Hz, acceleration ≤ 3.5 g Shock resistance 60–100 shocks/min, acceleration ≤ 4 g Mechanical life 100,000 operations (no load) Electrical life 50,000 operations (at rated load)
Manufacturer Product Page
ZLJM-400D 2Z Switching capacity — 400 ACoil power — max. 18 WApprovals — UL (E145623)Technical Specifications Model No. ZLJM-400D/2Z Contact arrangement DPDT Contact material AgCdO(12) Contact rating (resistive load) 400 A 80 V DC / 400 A 250 V AC Max. switching voltage 80 V DC, 250 V AC Max. switching power 10,000 VA Overload endurance (7 Ie / 10 s) 2400 A / 10 s Coil rated voltage 12, 24, 48, 60, 120 V DC, etc. Pick-up voltage 40–70 % of rated coil voltage Drop-out voltage 5–30 % of rated coil voltage Contact voltage drop ≤ 30 mV at 100 A Insulation resistance Min. 100 MΩ at 500 V DC Dielectric strength (between insulated parts) 1500 V AC 50/60 Hz (1 min) Operate time Max. 50 ms Release time Max. 50 ms Ambient temperature -25 … +60 °C Vibration resistance 10–200 Hz, acceleration ≤ 3.5 g Shock resistance 60–100 shocks/min, acceleration ≤ 4 g Mechanical life 100,000 operations (no load) Electrical life 50,000 operations (at rated load)
Manufacturer Product Page